Medical waste water monitoring

  1. What is medical sewage?

Medical wastewater is a solution discharged from a medical examination and treatment facility. Medical wastewater must be treated and disinfected before being discharged into the environment.

Sources receiving wastewater are surface water, coastal waters, drainage systems, where medical wastewater is discharged.

TT Parameter Unit

Value C

A B
1 pH 6,5 – 8,5 6,5 – 8,5
2 BOD5 (200C) mg/l 30 50
3 COD mg/l 50 100
4 Total suspended solids (TSS) mg/l 50 100
5 Sunfua (calculated by H2S) mg/l 1,0 4,0
6 Amoni (calculated by N) mg/l 5 10
7 Nitrat (calculated by N) mg/l 30 50
8 Phosphat (calculated by P) mg/l 6 10
9 Animal and vegetable fats and oils mg/l 10 20
10 Total radioactivity α Bq/l 0,1 0,1
11 Total radioactivity β Bq/l 1,0 1,0
12 Total coliforms MPN/ 100ml 3000 5000
13 Salmonella Bacteria/ 100ml KPH KPH
14 Shigella Bacteria/ 100ml KPH KPH
15 Vibrio cholerae Bacteria/ 100ml KPH KPH

– Column A specifies the C value of parameters and pollutants as the basis for calculating the maximum allowable value in medical wastewater when discharged to water sources used for domestic water supply..

– Column B specifies the C value of the parameters and pollutants as the basis for calculating the maximum allowable value in medical wastewater when discharged into water sources not used for domestic water supply..

– Medical wastewater discharged into a common sewer of a residential area is applied at the value of C specified in column B. In case medical wastewater is discharged into the collection system to lead to the concentrated wastewater treatment system, it must be sterilization, parameters and other contaminants apply according to the regulations of the unit managing and operating the centralized wastewater treatment system.

Cac chi tieu xet nghiem nuoc thai ma ban nen biet

QCVN is certified eligible environmental monitoring (VIMCERTS 197) Decree 27/2013 ND-CP.

QCVN is eligible for medical wastewater sampling and medical wastewater analysis services

To get a quotation of typical parameters of domestic wastewater, or environmental monitoring quotes, please contact 0919 98 48 39.

VIETNAM QCVN STANDARD TECHNICAL JOINT STOCK COMPANY

Address: 67/2/8 Rout 5, Ward 17, Govap District, Hochiminh City, Vietnam

Phone: 0287 308 6678 – Hotline: 0919 98 48 39

Email: info@qcvn.com.vn